An experimental study of air flow and temperature distribution in a room with displacement ventilation and a chilled ceiling

$
0
0
January 2013
Publication year: 2013
Source:Building and Environment, Volume 59

Displacement ventilation and chilled ceiling panel systems are potentially more energy efficient than conventional air conditioning systems and are characterized by the presence of vertical temperature gradients and significant radiant asymmetry. The characteristics of this type of system have been studied by making temperature and air flow measurements in a test chamber over a range of operating parameters typical of office applications. Results from the displacement ventilation study are consistent with other studies and show that normalized temperature profiles are independent of internal heat gain. Linear temperature gradients in the lower part of the room were found, in all cases, to be driven by convection from the adjacent walls. Significant mixing, indicated by reduced temperature gradients, was evident in the upper part of the room in the chilled ceiling results at higher levels of heat gain. Visualization experiments, velocity measurements and related numerical studies indicated that with greater heat gains the plumes have sufficient momentum to drive flow across the ceiling surface and down the walls. The significance of forced, as opposed to natural convection, is also suggested by relatively low Richardson Number (Ri) values found near the ceiling. Furthermore, in cases with moderately high internal gains, comparison of the temperature gradients indicated that the effect of ceiling surface temperature on the degree of mixing and the magnitude of the temperature gradient were of secondary importance. These findings are in contrast to the view that it is natural convection at the ceiling that causes enhanced mixing.

Highlights

► Test chamber experiments have been conducted. ► Chilled ceiling and displacement ventilation is characterized. ► Ceiling convection and mixing are examined. ► Ceiling convection tends to be forced in nature. ► Plume momentum induces mixing at higher heat gains.

Viewing all articles
Browse latest Browse all 2381

Trending Articles