Publication date: 1 May 2016
Source:Building and Environment, Volume 100
Author(s): Haida Tang, Xiao-Hua Liu, Haoyue Li, Yan Zhou, Yi Jiang
In this paper, the size of droplets departing from the superhydrophobic surface and conventional aluminum alloy surfaces was studied experimentally. It showed that the coalescence-induced jumping condensate droplets departing from the superhydrophobic surface has a radius of below 300 μ m, and the radii of the gravity-induced falling droplets from conventional aluminum alloy surfaces range from 2000 μ m to 7000 μ m. During droplets' dripping from radiant ceiling to human skin, numerical simulation also indicated that the change of the droplet size is rather small and can be neglected. Furthermore, the human sensory threshold size for fallen droplets was found to be a radius of 325 μ m via a psychological experiment conducted with 30 volunteers. Therefore, these results revealed that the superhydrophobic surface can significantly reduce condensation risks of radiant cooling ceiling systems. This is because the radii of coalescence-induced fallen condensate droplets from superhydrophobic surfaces are below this threshold, whereas gravity-induced falling droplets from conventional radiant ceiling surfaces can be perceived with a probability of over 95%.
Source:Building and Environment, Volume 100
Author(s): Haida Tang, Xiao-Hua Liu, Haoyue Li, Yan Zhou, Yi Jiang