Simulating air distribution and occupants' thermal comfort of three ventilation schemes for subway platform

$
0
0
Publication date: 15 November 2017
Source:Building and Environment, Volume 125
Author(s): Changping Liu, Angui Li, Changqing Yang, Wenrong Zhang
Excellent air distribution is an indispensable factor to acquire comfortable environment in high density occupant areas, such as subway stations. This study assesses the air distribution by adopting three different air supply schemes (mixing ventilation, stratified air ventilation and air curtain ventilation) for a subway platform. The simulation results are discussed in detail by considering air velocity, air temperature, age of air and Relative Warmth Index (RWI). It was demonstrated that air curtain ventilation presented an appropriate velocity and temperature distribution, which provides a healthy and comfortable environment. Focusing on the air curtain ventilation scheme, four cases were investigated to indicate the air velocity and temperature distribution in the occupied region. It is indicated that the highest velocities and the lowest temperatures were both achieved at the height of 0.2 m above the floor. Dimensionless velocity with different air supply velocity was proposed in this paper. This research is applicable for air curtain ventilation design appropriate for subway platform.