Quantcast
Channel: ScienceDirect Publication: Building and Environment
Viewing all articles
Browse latest Browse all 2381

Performance analysis of pulsed flow control method for radiant slab system

$
0
0
Publication date: January 2018
Source:Building and Environment, Volume 127
Author(s): Haida Tang, Paul Raftery, Xiaohua Liu, Stefano Schiavon, Jonathan Woolley, Fred S. Bauman
We present a novel pulsed flow control method (PFM) using a two-position valve to regulate the capacity of radiant slab systems. Under PFM, the on-time duration of the valve is short (compared to all prior work, e.g. 4-minute), and fixed, while the off-time varies. We present a novel, open-source, finite difference model that assesses three-dimensional transient slab heat transfer, accounting for the transient heat storage of the pipe fluid. Sensitivity analysis results indicate the dominant factors influencing energy performance of the PFM are: on-time duration; pipe diameter; and spacing. We experimentally validated both the new control strategy and model in full-scale laboratory experiments. Compared with previous intermittent control strategies (with on-time durations over 30 min), at 50% part load the PFM reduces 27% required water flow rate and increases supply to return water temperature differential. Compared with the variable temperature control method, at 50% part load the PFM reduces 24% required water flow rate. The energy performance of PFM is comparable to that of a conventional variable flow rate control. However, it has more accurate capacity control, achieves a more uniform surface temperature distribution, and reduces initial investment by substituting two-position for modulating valves, thus showing promise for engineering applications.

Graphical abstract

image

Viewing all articles
Browse latest Browse all 2381

Trending Articles